LAY-OUT OF
FLUE GAS OUTLET
AND CHIMNEY

 

 

   UDLÆGNING AF
RØGGASAFGANG
OG SKORSTEN


Flue Gas Outlet & Chimney
Røggasafgang & Skorsten

Recommended values in the arrangement
Anbefalede værdier i arrangementet
 

Maximum
Net Heat Capacity
[kW]
Flue Gas Piping
Min. Dimensions
A [mm]
Chimney / Stack
Min. Dimensions
B [mm]
80 200 200
500 250 250
600 300 300
700 300 350
900 350 400
1.200 350 450
1.500 400 500
1.700 450 500
2.300 500 550
3.500 550 600
4.000 600 650
4.500 650 700
5.000 700 750
6.000 700 800
7.000 750 850

 

 

Note 1 Height minimum 2 meters above roof surface and any roof of any buildings in a distance of 100 meter or according to local requirements. For gas combustion these recommendations can often be less restrictive.

contact

 

 

main menu

 


 


 

 

 

Note 2 Chimney should be supported sufficiently at bottom and at top based on strength calculations performed. Insulation thickness (2 x) according to local requirements, to be added the necessary diameter "B".
Note 3 Flue pas piping to be as short as possible, and bends as few as possible - preferable maximum two bends in the flue gas piping.

Angel of bends to be minimum 120° everywhere.
Note 4 Above heat capacities are net output, based on AB&CO high standard efficiencies. Diameters given are approximate value. In case of doubts, use a size higher.